18
18
NV10P - Manual - 01 - 2015
TECHNICAL DATA
Overvoltage - 59 for inductive VTs versions
Common confi guration:
59 Operating logic (Logic59) AND/OR
U> Element
U> Curve type (U>
Curve
) DEFINITE/INVERSE
[1]
Defi nite time
59 First threshold defi nite time (
U
>
def
) 0.50...1.50 U
n
(step 0.01 U
n
)
U>
def
Operating time (t
U
>
def
) 0.03...100.0 s
0.03...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Inverse time
59 First threshold inverse time (
U
>
inv
) 0.50...1.50 U
n
(step 0.01 U
n
)
U>
inv
Operating time (t
U
>
inv
) 0.10...100.0 s
0.10...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
U>> Element
Defi nite time
59 Second threshold defi nite time (
U
>>
def
) 0.50...1.50 U
n
(step 0.01 U
n
)
U>>
def
Operating time (t
U
>>
def
) 0.03...100.0 s
0.03...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time ≤ 0.04 s
Dropout ratio 0.95...0.98
Dropout time ≤ 0.04 s
Overshoot time 0.03 s
Pickup accuracy ± 1% ± 1% U
n
/E
n
Operate time accuracy 5% or ± 10 ms
Overvoltage - 59 for electronic sensor versions
Common confi guration:
Voltage measurement type for 59 (Utype59) U
ph-ph
/U
ph-n
59 Operating logic (Logic59) AND/OR
U> Element
U> Curve type (U>
Curve
) DEFINITE/INVERSE
[2]
Defi nite time
59 First threshold defi nite time (
U
>
def
) 0.50...1.50 U
n
/E
n
(step 0.01 U
n
/E
n
)
U>
def
Operating time (t
U
>
def
) 0.03...100.0 s
0.03...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Inverse time
59 First threshold inverse time (
U
>
inv
) 0.50...1.50 U
n
/E
n
(step 0.01 U
n
/E
n
)
U>
inv
Operating time (t
U
>
inv
) 0.10...100.0 s
0.10...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
U>> Element
Defi nite time
59 Second threshold defi nite time (
U
>>
def
) 0.50...1.50 U
n
/E
n
(step 0.01 U
n
/E
n
)
U>>
def
Operating time (t
U
>>
def
) 0.03...100.0 s
0.03...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time ≤ 0.04 s
Dropout ratio 0.95...0.98
Dropout time ≤ 0.04 s
Overshoot time 0.03 s
Pickup accuracy ± 1% ± 1% U
n
/E
n
Operate time accuracy 5% or ± 10 ms
Note 1 The mathematical formula for INVERSE curve is: t = (0.5 ∙ t
U
>
inv
) / [(U/U>
inv
) - 1]
t = operating time (in seconds)
t
U
>
inv
= operating time setting (in seconds)
U = input voltage
U>
inv
= threshold setting
Note 2 The mathematical formula for INVERSE curve is: t = (0.5 ∙ t
U
>
inv
) / [(U/U>
inv
) - 1]
t = operating time (in seconds)
t
U
>
inv
= operating time setting (in seconds)
U = input voltage
U>
inv
= threshold setting