EasyManua.ls Logo

Toro EVOLUTION Series - Valve, Pump Relay and Sensor Installation

Toro EVOLUTION Series
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8
Valve, Pump Relay and Sensor Installation
Figure 13
1 2
MV PUMP
SENSOR
SENSOR
COM
COM
Step 1 Route valve wires from the valves, master valves, pump relay and/or sensor into the controller cabinet.
Note: 18 AWG (1.0 mm
2
) multi-wire sprinkler valve connection cable can be used. is cable is insulated for direct burial
and is color-coded to simplify installation. It can be routed directly into the controller through the access hole provided for
valve wire conduit (if conduit is not used).
Step 2 $POOFDUWBMWFTNBTUFSWBMWFTBOEQVNQTUBSUSFMBZUPUIFWBMWFXJSFT - Connect the white color-coded wire from the cable
to one wire from each valve solenoid and/or pump relay. (Either of the two wires from the solenoid or pump relay can be used
for this connection.) is connection will be designated as the valve common wire.
Connect a separate cable wire to the remaining wire from each valve solenoid. Note the wire color-code used for each valve and
the zone it controls. You will need this information when connecting the valve wires to the controller.
$POOFDUTFOTPSUPUIFWBMWFXJSFT - Connect any two unused color-coded wires to the sensor. Note the color-code of the
sensor wires for installation.
Step 3 Secure all wire splices using wire nut connectors. To prevent corrosion and possible short circuits, always use an insulated wire
nut, grease cap or similar waterproong method.
Step 4 $POOFDUWBMWFTXJSFTUPUIFDPOUSPMMFS- Secure the valve common wire (white) to either of the two terminals labeled COM.
Secure the individual valve wires to the appropriate zones they control, Zone 1 valve to terminal 1, Zone 2 valve to terminal 2, etc.
$POOFDUNBTUFSWBMWFQVNQSFMBZXJSFTUPUIFDPOUSPMMFS- Secure the valve common wire (white) to either of the two
terminals labeled COM. Secure the Master Valve or Pump Relay wire to the terminal labeled .716.1.
$BVUJPO To prevent controller damage, do not connect the pump motor starter directly to the controller.
$POOFDUTFOTPSXJSFTUPUIFDPOUSPMMFS- Remove the jumper wire from the SENSORS terminals. Secure the two sensor wires
to the sensor terminals. Refer to the provided sensor instructions for further installation instructions.
Step 5 Test for proper operation.

Other manuals for Toro EVOLUTION Series

Related product manuals