232 GX9 ASD Installation and Operation Manual
OL1 ASD Overload Acceleration time is too short.
DC Injection current is too high.
Improper V/f setting.
Motor running during restart.
ASD or the motor is improperly matched to the application.
OL2 Motor Overload Improper V/f setting.
•Motor is locked.
Continuous operation at low speed.
Load requirement exceeds ability of the motor.
Startup frequency setting adjustment required.
OLR Dynamic Braking
Resistor Overload
Deceleration time is too short.
DBR setting adjustment required.
Over-Voltage Stall setting adjustment required.
OP1 Over-Voltage During
Acceleration
Motor running during restart.
OP2 Over-Voltage During
Deceleration
Deceleration time is too short.
DBR value is too high.
DBR required (DBR setup required).
Stall protection is disabled.
3-phase input voltage is out of specification.
Input reactance required.
OP3 Over-Voltage During
Fixed Speed
Load fluctuations.
3-Phase input voltage out of specification.
DBR required (DBR setup required).
OT Over-Torque A torque requirement by the load in excess of the setting of F616 or F617 for
a time longer than the setting of F618.
The ASD is improperly matched to the application.
The load is obstructed.
SEAL
Virtual Linear Pump
Sealing Water Error
Inadequate pump seal water.
Loss of pump seal water.
UP1
Main Power
Under-Voltage
Input 3-phase voltage is too low.
Momentary power failure longer than the time setting of F628.
UP2 Control Power
Under-Voltage
This fault is caused by an under-voltage condition at the 5, 15, or the 24 VDC
supply.
3-phase input voltage low.
LED Screen LCD Screen Possible Causes/Troubleshooting