GX9 ASD Installation and Operation Manual 69
Command Control Selections
The following is a listing and description of the
Command Mode (F003) selections (Program
Fundamental Standard Mode Selection Command
Mode).
Settings:
Terminal Board (default setting)
Allows for Command control input via the 25-pin terminal strip on the Terminal Board.
CN8 Option
Allows for Command control input via the CN8 connector of the Control Board.
Common Serial (TTL)
Set the EOI Port Address to TTL to use this feature.
RS232/RS485
Set the EOI Port Address to RS232/RS485 to use this feature.
Communication Card
Routes the control and monitoring I/O to CNU3 of the Control Board of the GX9 ASD
(Communication Card connector).
Frequency Control Selections
The following is a listing and description of the
Frequency Mode (F004) selections (Program
Fundamental Standard Mode Selection
Frequency Mode).
Settings:
VI/II
0 to 10-volt DC analog input connected to VI or a
4 – 20 mA (or 0 to 1 mA) DC input current connected to II (cannot use both simultaneously).
RR (default setting)
0 to 10-volt DC analog input connected to RR.
RX
-10 to +10-volt DC analog input connected to RX.
RX2 Option
-10 to +10-volt DC analog input connected to RX2.
CN8 Option
Allows for Frequency control input via the CN8 connector of the Control Board.
Binary/BCD Input
Allows for discrete input terminal input to control the ASD output.
Common Serial (TTL)
To use the EOI for control requires that the EOI Port Address be set to TTL to use this feature.