EasyManua.ls Logo

Toshiba GX9 - Voltage;Current Specifications

Toshiba GX9
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GX9 ASD Installation and Operation Manual 237
Voltage/Current Specifications
Note: The Short Circuit Current Rating for the all items is 85.0 kA if no circuit breaker is
used.
Table 16. Voltage/Current Specifications for the GX9 ASD.
Model
Number
GX96
HP
Rated
kVA
kW
3-P Input
50/60 Hz
±2%
3-P Output
Variable
Frequency
Output
Current Amps
100% FLA/
110% Cont.
Output
Current Amps
130%
120 Seconds
Output
Current Amps
150%
60 Seconds
060 5.0 5.0 6.0
525 - 690 VAC
(±10%)
Input VAC
Level Max.
6.1/6.7
N/A
9.2
080 7.5 7.5 7.5
9.0/9.9 13.5
110 101010
12/13.2 18.0
160 151515
17/19 25.5
220 202020
22/24 33.0
270 25 25 25
27/30 40.5
330 303030
32/35 48.0
400 404040
41/45 61.5
500 505050
52/57 78.0
600 606060
62/68 93.0
750 757575
77/85 116
10K 100 100
90 96/106 144
12K 125 120
110 118/130 177
15K 150 150
132 144/158 187.2
N/A
17K 175 175
160 168/185 218.4
20K 200 200
200 196/216 254.8
25K 250 250
250 247/172 321.1
30K 300 300
315 304/334 395.2
40K 400 400
400 384/422 499.2
50K 500 500
450 481/529 625.3
60K 600 600 600
601/661 781.3
70K 700 700 700
698/768 907.4
80K 800 800 800
770/847 1001
90K 900 900 900
866/953 1125.8
10L 1000 1000 1000
962/1058 1250.6
12L 1200 1200 1200
1155/1271 1501.5

Table of Contents