Table 5: Input Terminal Selections
Setting
Value
Data
(Hex)
Function Setting
Value
Data
(Hex)
Function
0 10C8 R (reverse run) 28 04AF Binary bit #6
1 011C SS1 (preset speed selection) 29 08AF Binary bit #7
2 021C SS2 (preset speed selection) 30 10AF Binary bit #8
3 041C SS3 (preset speed selection) 31 20AF Binary bit #9
4 081C SS4 (preset speed selection) 32 40AF Binary bit #10
5 20C8 F (forward run) 33 04CE No effect
6 201B RES (fault reset) 34 01C7 UP/DOWN frequency setting (UP)
7 C0C9 ST (gate ON/OFF) 35 02C7 UP/DOWN frequency setting
(DOWN)
8 0CC8 JOG selection 36 04C7 UP/DOWN frequency clear
9 081A Acc/dec #1/#2 selection 37 08C7 PUSH-type RUN key
10 101B Emergency off 38 10C7 PUSH-type STOP key
11 021B DC injection braking ON/OFF 39 02B9 No effect
12 041B Fundamental parameter
switching (V/F #2)
40 C0C8 Forward/reverse run selection
13 011B Feedback control ON/OFF 41 20C7 RUN
14 10CE Pattern run selection #1 42 30C9 Binary data write
15 20CE Pattern run selection #2 43 0198 [LOCAL/REMOTE] key
16 40CE Pattern run selection #3 44 0298 [MON] key
17 80CE Pattern run selection #4 45 0498 [PRG] key
18 02CE Pattern run continue signal 46 0898 [UP] (s) key
19 01CE Pattern run step trigger signal 47 1098 [DOWN] (t) key
20 0AC9 JOG forward run 48 2098 [READ/WRITE] key
21 06C9 JOG reverse run 49 4098 [RUN] key
22 10AE Binary bit #0 50 8098 [STOP/CLEAR] key
23 20AE Binary bit #1 51 08CE Commercial power / inverter
switching signal
24 40AE Binary bit #2 52 40C7 Reserved for option use
25 80AE Binary bit #3 53 10CB RR frequency switching input
26 01AF Binary bit #4 54 20CB IV frequency switching input
27 02AF Binary bit #5
Note: In order for binary bit #0 #10 (setting values 22 32) and UP/DOWN frequency setting (setting values 34 &
35) inputs to be valid, parameter FREQUENCY PRIORITY SELECTION #1 or FREQUENCY PRIORITY
SELECTION #2 in GROUP:FREQUENCY SETTING PARAMETERS must be set to 5 (BIN (binary setting
or UP/DOWN setting)).