Trane TCONT900AC43UA - Electrical Connections to a Communicating Systems Air Handler in Conventional 24 V Mode

Trane TCONT900AC43UA
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AC - A 6
Electronic Air Cleaners
BAYTRANS12024 Transformer
• Transformer must have a grounded 120 VAC power source. Do not defeat ground plug on the transformer.
• Mount transformer to building structure with the four provided wood screws.
Note: For systems order a 120 VAC to 24 VAC transformer, KIT# BAYTRANS12024 to provide 24 volt power
only to the air cleaner. Access to 120 VAC outlet is required.
Figure 3
Transformer not applicable to 50 Hz units.
Electrical Connections To A Communicating Systems Air Handler In Conventional 24V Mode
WARNING
Hazardous Voltage. Disconnect all electric power,
including remote disconnects before servicing. Fol-
low proper lockout/tagout procedures to ensure the
power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death
or serious injury.
STEP 1
Remove electrical power going into the air handler.
STEP 2
On the communicating systems air handler, remove
the blower access panel.
STEP 3
Remove the communicating control box cover.
STEP 4
Locate the red jumper wire which is attached from
EAC to R on the Communicating Systems PCB.
Confirm it is connected. If there is not a jumper wire
installed, then one must be installed in this location
in order for the air cleaner to function properly.
STEP 5
Replace the Communicating control box cover.
STEP 6
Locate the white wire coming from the Communicating
System Air Handler PCB labeled “EAC”. The wire will
have a male spade terminal connected to it and a
female spade terminal inserted into the male terminal.
Remove the female spade terminal and crimp it to the
green wire on the air cleaner harness.