R - A 27
Alert Code Response
EEV fault LED 3 flash
Problem Description
Suction pressure transducer fault
- Valve will close and LPCO will trip
Possible Causes/Solutions
Suction pressure transducer input is out of range
- Compare DC voltage to sensor chart in literature
EEV fault LED 4 flash
Problem Description
Suction temperature sensor fault
- Valve will close and LPCO will trip
Possible Causes/Solutions
Suction temperature sensor is out of range
- Compare DC voltage to sensor chart in literature
EEV fault LED 5 flash
Problem Description
EEV stepper motor coil fault
- Power supply will shut down to protect board
Possible Causes/Solutions
EEV stepper motor coil is shorted
Wiring to stepper motor coil is shorted
EEV fault LED 7 flash
Problem Description
EEV is responding but system not performing prop-
erly
Possible Causes/Solutions
System refrigerant charge low
Restriction in refrigerant circuit
EEV fault LED 8 flash
Problem Description
EEV controller senses superheat less than 3° with
valve in the minimum position during an active call for
compressor heat
Possible Causes/Solutions
Compressor either not running or running but not
pumping
EEV fault LED 9 flash
EEV Control Board = 9 Flash
Problem Description
EEV controller senses superheat below 3° for at least
ten minutes in cooling mode of operation
Possible Causes/Solutions
Indoor metering device not operating properly
Low indoor air flow
Refrigerant circuit restriction
EEV fault LED 1 flash
Problem Description
EEV stepper motor coil fault
Possible Causes/Solutions
EEV stepper motor coil is open or has an intermittent
short
Wiring to stepper motor coil is open or has an
intermittent short
EEV fault LED 2 flash
Problem Description
Internal control fault
Possible Causes/Solutions
Replace EEV control board
EEV fault LED 6 flash
Problem Description
EEV is not responding to a request for position change
Possible Causes/Solutions
EEV is stuck
- Faulty, overheated or debris in refrigerant circuit
EEV fault LED 10 flash
EEV Control Board = 10 Flash
Problem Description
Not used at this time