Trane TCONT900AC43UA - Error 101: Y1 Relay Fault; Error 104: Heater Relay Fault

Trane TCONT900AC43UA
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
R - A 13
Alert Code Response
Error 101: Y1 relay fault
Comfort Control = Err 101
User Interface = Y1 OFF ERR
Air Handler Fault LED = 7 Flash
or
Furnace Fault LED = No Fault Reported
Problem Description
Y1 relay on indoor unit control board is “OFF” with a
call for cooling
- If comfort control is setup for single stage cooling
and a communicating outdoor unit is not discovered
on the communicating bus, the Y1 relay on the indoor
control board will apply 24v to Y1 terminal on a active
call for cooling
Possible Causes/Solutions
Internal control failure
Replace control board
Error 93: Gas valve fault
Comfort Control = Err 93
User Interface = INT GV ERR
Furnace Fault LED = Solid ON
Problem Description
Control board sensing voltage when voltage should
not be present
Possible Causes/Solutions
Replace furnace control board
Error 101: Y1 relay fault
Comfort Control = Err 101
User Interface = Y1 ON ERR
Air Handler Fault LED = 7 Flash
or
Furnace Fault LED = No Fault Reported
Problem Description
Y1 relay on indoor unit control board is “ON” without a
call for cooling
- If comfort control is setup for single stage cooling
and a communicating outdoor unit is not discovered
on the communicating bus, the Y1 relay on the indoor
control board will apply 24v to Y1 terminal on a active
call for cooling
Possible Causes/Solutions
24 volts sensed on Y1 terminal of low voltage terminal
board without an active call for cooling
24 volts applied to Y1 terminal when a
communicating outdoor unit is installed
Onboard Y1 relay stuck closed
- Replace control board
Error 104: Heater relay fault
Comfort Control = Err 104
User Interface = HT OFF ERR
Air Handler Fault LED = 4 Flash
Problem Description
Heat relay on indoor unit control board is stuck open
- The heat relay provides a 24volt input to each bank
of electric heat when a call for auxiliary heat is present
Possible Causes/Solutions
Replace control board