(A/T)CONT900AC43UA Installer Guide
4 Heat/3 Cool/ Heat Pump
Communicating Programmable 3-Wire Hookup
toggle between the main screen and a screen show-
ing the Alert code number. When multiple Alert codes
exist simultaneously, the display will cycle through
each code (showing a maximum of the five most re-
cent Alerts) and return to the main screen.
Equipment damage hazard. Minimum
compressor off-time is bypassed during Installer
System Test.
Avoid cycling compressor quickly. Observe compres-
sor protection period.
System checkout
Installer system test
The Installer System Test mode is used to test the
Comfort Control operation with HVAC equipment
(See Table 6, Pages 19-20.) System configuration
determines which tests are available and the num-
ber of stages shown. While in System Test mode,
the minimum off time is bypassed.
The Installer Test is part of the Installer Setup op-
tions. Enter Installer Setup screen and press the
Down arrow key for quick access to the test
selection(s).
Changing tests will turn equipment off.
Entering Installer Setup will turn equipment off.
Charge Assist™ mode not available during
Installer System Tests.
Test modes times out after five minutes.
Advanced features
Adjustable continuous air flow
The Continuous Fan air flow is user adjustable from
25% to 100% in 5% increments either by entering
the User Setup menu or the Installer Setup menu
(See Table 4, ISU Number 0186, Page 10.)
Continuous fan mode during cooling operation
may not be appropriate in humid climates. If the
indoor air exceeds 60% relative humidity or sim-
ply feels uncomfortably humid, it is
Table 6. Installer System Tests.