Alert Code Response
Error 126: Equipment change alert
Comfort Control = Err 126
User Interface = No Alert Displayed
Outdoor Unit Fault LED = No Fault Reported
Problem Description
Equipment does not match value stored at startup
- When communicating systems are initially powered
the comfort control will auto discover and remember
all equipment (outdoor unit, indoor unit) reported on
the communication bus
- A Telephone Access Module (TAM) will not create
this alarm
Possible Causes/Solutions
Outdoor unit breaker tripped
OD transformer or fuse open
Field low voltage wiring open to outdoor unit
Error 139: 24v communication mismatch
Comfort Control = Err 139
User Interface = 24v COM MSMTCH
Furnace Fault LED = 10 Flash
Problem Description
Mode has been set incorrectly on User Interface
- This fault only applies to communicating 80%
furnaces
Possible Causes/Solutions
Comfort control mode on the furnace user interface is
set for 24v when installed with communicating
comfort control
- If installed as part of a communicating system, the
comfort control mode must be set to communicating
(COMM)
Pressure switch failure
Comfort Control = No Error Code Displayed
User Interface = PS1 CLOSED
Furnace Fault LED = 3 Flash
Problem Description
First stage pressure switch closed when the switch
should be open
Possible Causes/Solutions
Pressure switch contacts stuck closed
Draft inducer motor running with no call for heat
Improper wiring to pressure switch
Pressure switch failure
Comfort Control = No Error Code Displayed
User Interface = PS2 OPEN
Furnace Fault LED = 3 Flash
Problem Description
Second stage pressure switch will not close
Possible Causes/Solutions
Pressure switch contacts stuck open
Pressure switch tubing not connected or restricted
Vent piping restricted or improperly sized
Flue gas condensate backing up in secondary heat
exchanger
Miscellaneous alert codes
Pressure switch failure
Comfort Control = No Error Code Displayed
User Interface = PS1 OPEN
Furnace Fault LED = 3 Flash
Problem Description
First stage pressure switch will not close
Possible Causes/Solutions
Pressure switch contacts stuck open
Pressure switch tubing not connected or restricted
Vent piping restricted or improperly sized
Flue gas condensate backing up in secondary heat
exchanger