R - A 17
Alert Code Response
Error 114: PM bad or missing
Comfort Control = Err 114
User Interface = ID MTR ERR
Air Handler Fault LED = 2 Flash
or
Furnace Fault LED = No Fault Reported
Problem Description
Blower horsepower does not match blower
specifications stored in the indoor Personality Module
(PM) data files
Possible Causes/Solutions
Incorrect blower horsepower for unit applied
Incorrect PM for unit applied
- If the blower motor and PM are correct, replace the
blower motor
Error 114: PM bad or missing
Comfort Control = Err 114
User Interface = No Alert Displayed
Outdoor Unit Fault LED = 14 Flash
Problem Description
Outdoor unit Personality Module (PM) data corrupt
or Personality Module (PM) missing
- System will continue to operate with this error if
original PM data has not been corrupted but a fault will
be displayed on comfort control
Possible Causes/Solutions
Outdoor PM is either not connected or connected but
not seated properly
Incorrect PM for model family connected
- Verify model/serial number on PM sticker matches
with unit applied
PM could be corrupted due to power surge or
damaged due to faulty field wiring
- Disconnect power, reconnect PM, then reapply power
to unit; if error does not clear replace PM
Error 114: PM bad or missing
Comfort Control = Err 114
User Interface = No Alert Displayed
Air Handler Fault LED = 2 Flash
Problem Description
Air Handler Personality Module (PM) data corrupt
or Personality Module (PM) missing
- System will continue to operate with this error if
original PM data has not been corrupted but a fault will
be displayed on comfort control
Possible Causes/Solutions
Indoor PM is either not connected or connected but
not seated properly
PM could be corrupted due to power surge or
damaged due to faulty field wiring
- Disconnect power, reconnect PM, then reapply power
to unit; if error does not clear replace PM
Error 125: Input Ac voltage fault
Comfort Control = Err 125
User Interface = No Alert Displayed
Air Cleaner Fault LED = YEL-2, 3 & 4 OFF
RED-1 ON, 2 &3 OFF
Problem Description
Input AC voltage is at or below 22vAC while under load
Possible Causes/Solutions
Ensure proper sized transformer is installed
- 75va for air handlers
- 50va for furnaces
Check low voltage wiring to air cleaner