CA - A 15
Charge Assist™
Troubleshooting Charge Assist
TM
Control
LED Flash Codes
If the comfort control is displaying Err code 89 or 91 or
if the Charge Assist™ control fault LED is flashing a
one flash code go to troubleshooting procedures for
Err code 89 or 91
Fault LED flash codes of 2, 3 or 4 flashes
Go to defrost control troubleshooting procedures.
These faults are not reported to the Comfort Control
as Err codes.
Fault LED flash code of 5, Err code 67
Will be displayed at the Comfort Control. The fault
LED (Figure 36) will be flashing in groups of five flashes.
This indicates that the outdoor Ambient Temperature
Sensor is reading out of range.
At the Charge Assist™ Control, read the DC voltage
at the Ambient Temperature Sensor plug J7 with the
sensor plugged in or unplug the sensor and read the
resistance of the sensor (Figure 37).