R - A 19
Alert Code Response
Pressure switch failure
Comfort Control = No Error Code Displayed
User Interface = PS2 CLOSED
Furnace Fault LED = 3 Flash
Problem Description
Second stage pressure switch closed when the switch
should be open
Possible Causes/Solutions
Pressure switch contacts stuck closed
Draft inducer motor running with no call for heat
Improper wiring to pressure switch
Pressure switch failure
Comfort Control = No Error Code Displayed
User Interface = PS3 OPEN
Furnace Fault LED = 3 Flash
Problem Description
Third stage pressure switch will not close
Possible Causes/Solutions
Pressure switch contacts stuck open
Pressure switch tubing either not connected or
restricted
Vent piping restricted or improperly sized
Flue gas condensate backing up in secondary heat
exchanger
Pressure switch failure
Comfort Control = No Error Code Displayed
User Interface = PS3 CLOSED
Furnace Fault LED = 3 Flash
Problem Description
Third stage pressure switch closed when the switch
should be open
Possible Causes/Solutions
Pressure switch contacts stuck closed
Draft inducer motor running with no call for heat
Improper wiring to pressure switch
Low flame signal
Comfort Control = No Error Code Displayed
User Interface = LO FLAME SNS
Furnace Fault LED = 8 Flash
Problem Description
Flame current is low, but still strong enough to allow
operation
- 1.0 micro amp is the minimum flame current to
allow operation
Possible Causes/Solutions
Flame sensor needs to be cleaned
Flame sensor not properly positioned in flame
Flame sensor wire has high resistance
Low gas pressure causing weak flame
Twinning error
Comfort Control = No Error Code Displayed
User Interface = TWIN ERROR
Air Handler Fault LED = 8 Flash
or
Furnace Fault LED = No Fault Reported
Problem Description
Multiple variable speed indoor units twinned together
Possible Causes/Solutions
Variable speed indoor units cannot be twinned