R - A 20
Alert Code Response
Flame lost or ignition failed
Comfort Control = No Error Code Displayed
User Interface = RETRY
Furnace Fault LED = 2 Flash
Problem Description
Flame sensor does not sense flame
- After 3 retries within the same call for heat an ERR22
will be displayed on the comfort control and RETRY
LO will be displayed on user interface
Possible Causes/Solutions
Flame sensor not sensing flame
- Less than one microamp
Inlet gas pressure too low
Outlet gas pressure too low
Flame sensor not positioned properly in flame
Burner crossovers not aligned properly or restricted
Line polarity fault
Comfort Control = No Error Code Displayed
User Interface = POLARITY ERR
Furnace Fault LED = 6 Flash
Problem Description
Line voltage polarity reversed
- Due to software limitations, reversed polarity faults
(POLARITY ERR) and grounding faults (GND FAULT)
will occur simultaneously
Possible Causes/Solutions
Line hot (120v to ground) and line neutral (less than
8v to ground) are reversed
- Also see GND FAULT for additional causes
A/C line fault
Comfort Control = No Error Code Displayed
User Interface = AC VOLTS LOW
Furnace Fault LED = No Fault Reported
Problem Description
Line voltage to furnace is too low (less than 70vAC)
Possible Causes/Solutions
Improper voltage from main power supply
Faulty breaker or switch
A/C line fault
Comfort Control = No Error Code Displayed
User Interface = AC VOLTS HI
Furnace Fault LED = No Fault Reported
Problem Description
Line voltage to furnace is too high (136vAC)
- Due to software limitations, ignitor faults
(IGNITOR ERR) and high voltage faults (AC Volts Hi)
will occur simultaneously
Possible Causes/Solutions
Improper voltage from main power supply
- Also see IGNITOR ERR for additional causes
Flame lost or ignition failed
Comfort Control = No Error Code Displayed
User Interface = RECYCLE
Furnace Fault LED = 2 Flash
Problem Description
Burners ignite and flame sensor circuit is proven then
burners drop out
- After 10 recycles within the same call for heat an
ERR22 will be displayed on the comfort control and
RECYCLE LO will be displayed on user interface
Possible Causes/Solutions
Gas valve solenoid failing
Inlet gas pressure dropping out
- Gas pressure regulator failing
- Debris in gas valve screen or blockage in
supply line
Air impingement on burners or flame