R - A 8
Alert Code Response
Error 53: Outdoor sensor missing
Comfort Control = Err 53
User Interface = No Alert Displayed
Outdoor Fault LED = No Fault Displayed
Problem Description
Outdoor temperature sensor is not reporting on the
communication bus
Possible Causes/Solutions
Outdoor unit not reporting on the communication bus
- Loss of power to outdoor unit
- Control transformer in outdoor unit has failed
ERR53 may be followed by an ERR126 if outdoor unit
is not reporting on the communication bus
Error 54: Faulty humidity sensor
Comfort Control = Err 54
User Interface = No Alert Displayed
Air Handler Fault LED = No Fault Reported
or
Furnace Fault LED = No Fault Reported
Problem Description
Internal humidity sensor in comfort control has failed
- If ISU370 indoor humidity sensor is disabled or set
to remote an Err54 will be displayed on comfort control
Possible Causes/Solutions
Replace comfort control
Failure could be caused by voltage spikes or
electrostatic discharge
Error 64: Stuck button(s)
Comfort Control = Err 64
User Interface = No Alert Displayed
Air Cleaner Fault LED = YEL-1, 2 & 3 ON
RED-1 & 2 ON, 3 OFF
Problem Description
One or more buttons on the air cleaner power door
are stuck ON
Possible Causes/Solutions
Check to see if buttons on air cleaner power door
operate smoothly without any obstructions
Replace air cleaner power door if unable to free
button or clear alert
Error 67: Temperature sensor fault
Comfort Control = Err 67
User Interface = No Alert Displayed
Outdoor Fault LED = 5 Flash
Problem Description
Ambient temperature sensor fault
Possible Causes/Solutions
Ambient Sensor open or shorted
- Zero or infinite resistance
Ambient Sensor out of range
- Compare resistance value of sensor to chart in
literature
No output voltage from control board to sensor
- With sensor disconnected, 5vDC should be
measured on control board