EasyManua.ls Logo

Trane TCONT900AC43UA - Page 307

Trane TCONT900AC43UA
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
R - B 13
Solving Err 91 Comm Errors
Does the comfort sensor and furnace IFC or air
handler now communicate?
Yes: Err 91 is being caused by the thermostat wire
or its routing. Repair, reroute or replace the
thermostat wire.
No: Replace the comfort sensor.
Step 8
Does the furnace IFC (See Figure 26) or air
handler fault LED show a fault flash code?
Yes: Go to Step 5.
No: Go to Step 9.
Figure 26
Step 9
Does the outdoor unit Charge Assist™ Control
have 24 volts AC at plug J2 terminals R and B?
(See Figure 27.)
Note: When any of the Charge Assist™ LEDs are
on or flashing, this only indicates that some low
voltage AC is present. Check the 24 volts AC supply
with a volt ohm meter.
Yes: Go to Step 10.
No: 24 volts AC is supplied by the outdoor unit’s trans-
former. Repair or replace as needed.
Figure 27
Step 10
Does the outdoor unit Charge Assist™ Control
fault LED show a fault flash code of one flash?
Yes: Check the DC voltage at test plug J2 terminals
D and B. If this voltage is 16 to 17 volts DC, this
indicates that the D or B or both thermostat wires
coming from the furnace or air handler are open (See
Figure 28.) Repair or replace the thermostat wire.
No: Normal voltage at this point is 12.5 volts DC.
Go to Step 11.

Table of Contents

Other manuals for Trane TCONT900AC43UA

Related product manuals