EasyManua.ls Logo

Trane Voyager TC* - Evaporator Fan Performance 15 Tons T*D181 C Dehumidification (Hot Gas Reheat Option) Downflow

Trane Voyager TC*
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RT-PRC024-EN 57
Performance Data
(15 Tons High Efficiency)
Table 39. Evaporator Fan Performance 15 Tons T*D181C Dehumidification (Hot Gas Reheat Option) Downflow
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor w/
Field Supplied Motor
Sheave
(i)
(i)
Field Supplied Fan Sheave BK160 Required. Field Supplied Belt may be necessary. Field Supplied Belt may be necessary.
3-HP Standard Motor
w/Field Supplied Motor
Sheave
(ii)
(ii)
Field Supplied Fan Sheave BK120 Required. Field Supplied Belt may be necessary. Field Supplied Belt may be necessary.
3-HP Standard Motor
w/Field Supplied Low
Static Drive Fan Sheave
3000* 295 0.26 346 0.35 391 0.45 432 0.56 471 0.68 506 0.80 539 0.92 569 1.04 596 1.17 622 1.30
3600* 333 0.40 379 0.51 420 0.62 458 0.74 494 0.87 527 1.00 559 1.14 589 1.28 617 1.43 644 1.57
4200* 373 0.60 415 0.72 452 0.85 487 0.98 520 1.12 551 1.26 581 1.41 610 1.57 638 1.73 664 1.89
4800 414 0.84 452 0.99 487 1.13 519 1.27 550 1.43 579 1.59 607 1.74 635 1.91 660 2.08 686 2.26
5400 455 1.14 491 1.32 524 1.48 554 1.64 582 1.80 610 1.98 637 2.15 662 2.33 687 2.51 710 2.70
6000 497 1.51 531 1.73 561 1.91 590 2.08 617 2.26 643 2.44 667 2.63 692 2.83 715 3.02 739 3.22
6600 540 1.96 572 2.20 601 2.42 628 2.61 653 2.80 678 2.99 701 3.20 724 3.41 746 3.61 768 3.83
7200 583 2.50 613 2.75 641 3.02 666 3.23 690 3.44 714 3.65 736 3.86 758 4.08 778 4.30 799 4.53
3-HP Standard Motor & Drive 5-HP Oversized Motor & Drive
Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3-HP Standard Motor & Drive 3-HP Standard Motor & High Static Drive Accessory
3000* 646 1.43 669 1.56 692 1.70 714 1.84 734 1.98 755 2.13 775 2.28 793 2.42 813 2.58 830 2.72
3600* 669 1.72 694 1.88 716 2.02 738 2.18 759 2.34 778 2.49 798 2.66 817 2.82 835 2.98 854 3.16
4200* 690 2.06 715 2.23 737 2.39 760 2.57 782 2.74 803 2.92 822 3.09 842 3.28 861 3.46 878 3.64
4800 711 2.44 735 2.63 758 2.81 780 3.00 802 3.19 823 3.38 843 3.58 864 3.78 882 3.97 901 4.17
5400 734 2.89 758 3.09 780 3.29 801 3.49 822 3.69 844 3.91 864 4.12 883 4.33 903 4.55 921 4.76
6000 761 3.42
(iii)
(iii)
3-HP Standard Motor & High Static Drive Accessory.
782 3.63 804 3.84 824 4.05 845 4.27 865 4.49 885 4.72 904 4.95 923 5.18 941 5.41
6600 789 4.05 810 4.26 831 4.49 850 4.71 870 4.94 889 5.18 908 5.41 927 5.65
7200 819 4.76 840 5.00 859 5.23 879 5.47 898 5.72
5-HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table 50.
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table 51.
For Oversized Evaporator Fan Speed (RPM), reference Table 53.
Fan motor heat (MBH) = 3.15 x Fan BHP.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to Table 54 to determine additional static pressure drop due to other options/accessories.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
*For 3000, 3600 and 4200 CFM, unit applications below 320 CFM/Ton are only applicable to TCD models only (No Gas Heat). See below for restrictions.
Electric heaters restricted on applications below 320 CFM/Ton.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 320 CFM/Ton.

Table of Contents