RT-PRC024-EN 81
Electrical Data
(High Efficiency)
Standard Indoor Motor Oversize Indoor Motor
Tons
Unit Model
Number
Heater Model
Number
Heater kW
Rating
Control
Stages Control
Max Fuse Size
or Max Circuit
Breaker MCA
Max Fuse Size
or Max Circuit
Breaker
25 TCD301CW AYDHTRMW36A 36.0 2 55 60
AYDHTRLW54A 54.0 2 77 80
AYDHTRKW72A 72.0 2 98 100
(i)
For Heater Model Numbers: AYDHTRK427A and AYDHTRL427A do not use oversized motor.
(ii)
Values do not include power exhaust accessory. *Applies only to Dehumidification (Hot Gas Reheat) Models.
Table 71. Electrical Characteristics Compressor Motor and Condenser Motor 60 Cycle
Compressor Motors Condenser Fan Motors
Amps
(i)
(i)
For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.
Amps
Tons
Unit Model
Number No. Volts Phase HP
(ii)
(ii)
HP for each compressor. *Indicates both downflow and horizontal units.
RPM RLA LRA No. Phase HP FLA LRA
12½ T/YC*151C3 2 208-230 3 5.70 3450 20.7 156 2 1 .50 3.2 8.8
T/YC*151C4 2 460 3 5.70 3450 10.0 75 2 1 .50 1.6 3.8
T/YC*151CW 2 575 3 5.70 3450 8.2 54 2 1 .50 1.3 3.2
15 T/YC*181C3 2 208-230 3 9.30/4.50 3450 31.5/16.9 253/124 2 1 .50 3.2 8.8
T/YC*181C4 2 460 3 9.30/4.50 3450 15.1/8.2 113/59.6 2 1 .50 1.6 3.8
T/YC*181CW 2 575 3 9.30/4.50 3450 12.1/6.6 85/49.4 2 1 .50 1.3 3.2
17½ T/YC*211C3 2 208-230 3 10.0/5.70 3450 33.3/20.7 278/156 2 1 1.00 5.5 18.3
T/YC*211C4 2 460 3 10.0/5.70 3450 16.3/10.0 124/75 2 1 1.00 2.9 9.3
T/YC*211CW 2 575 3 10.0/5.70 3450 13.2/8.2 92/54 2 1 1.00 2.0 5.7
20 T/YC*241C3 2 208-230 3 9.30 3450 31.6 253 2 1 1.00 5.5 18.3
T/YC*241C4 2 460 3 9.30 3450 16.1 113 2 1 1.00 2.9 9.3
T/YC*241CW 2 575 3 9.30 3450 12.9 85 2 1 1.00 2.0 5.7
25 T/YC*301C3 2 208-230 3 10.00 3450 37.6 278 2 1 1.00 5.5 18.3
T/YC*301C4 2 460 3 10.00 3450 18.3 124 2 1 1.00 2.9 9.3
T/YC*301CW 2 575 3 10.00 3450 14.9 92 2 1 1.00 2.0 5.7
Table 72. Electrical Characteristics Compressor Motor and Condenser Motor 60 Cycle TXV/Face-Split Evaporator Coil
Option (Downflow Only)
Compressor Motors Condenser Fan Motors
Amps
(i)
(i)
For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.
Amps
Tons
Unit Model
Number No. Volts Phase HP
(ii)
(ii)
HP for each compressor.
RPM RLA LRA No. Phase HP FLA LRA
12½ T/YCD151C3 2 208-230 3 5.7 3450 18.6 156 2 1 .50 3.2 8.8
T/YCD151C4 2 460 3 5.7 3450 9.4 75 2 1 .50 1.6 3.8
T/YCD151CW 2 575 3 5.7 3450 7.4 54 2 1 .50 1.3 3.2
15 T/YCD181C3 2 208-230 3 9.30/4.50 3450 32.1/16.4 253/124 2 1 .50 3.2 8.8
T/YCD181C4 2 460 3 9.30/4.50 3450 15.6/8.7 113/59.6 2 1 .50 1.6 3.8
T/YCD181CW 2 575 3 9.30/4.50 3450 12.3/7.4 85/49.4 2 1 .50 1.3 3.2
17½ T/YCD211C3 2 208-230 3 10.00/5.7 3450 34.8/19.5 278/156 2 1 1.00 5.5 18.3
T/YCD211C4 2 460 3 10.00/5.7 3450 17.0/10.3 124/75 2 1 1.00 2.9 9.3
T/YCD211CW 2 575 3 10.00/5.7 3450 13.8/8.1 92/54 2 1 1.00 2.0 5.7
20 T/YCD241C3 2 208-230 3 9.0/9.3 3500/3450 30.4/32.6 225/253 2 1 1.00 5.5 18.3
T/YCD241C4 2 460 3 9.0/9.3 3500/3450 16.1/16.8 114/113 2 1 1.00 2.9 9.3
T/YCD241CW 2 575 3 9.0/9.3 3500/3450 12.5/13.4 80/85 2 1 1.00 2.0 5.7
25 T/YCD301C3 2 208-230 3 10.00 3450 36.2 278 2 1 1.00 5.5 18.3
T/YCD301C4 2 460 3 10.00 3450 17.7 124 2 1 1.00 2.9 9.3
T/YCD301CW 2 575 3 10.00 3450 14.3 92 2 1 1.00 2.0 5.7
Table 70. (continued) Unit Wiring with Electric Heat (Single Point Connection) — TXV/Face-Split Evaporator Coil or
Dehumidification (Hot Gas Reheat) Refrigeration System (Downflow only)