3.DATA EXCHANGE WITH CPU
20
Near zero
“1” when Weight <= Near zero setting.
   Weight : Weight value Near zero
SP1, SP2, SP3
Simple comparison mode
SP1: “1” if Weight >= Final setting – Set point 1 setting
SP2: “1” if Weight >= Final setting – Set point 2 setting
SP3: “1” if Weight >= Final setting – FF CPS.setting
Sequence mode
Each bit is initialized to “1” when weighing sequence is started by SEQ Start’s
ON edge.
SP1: “0” if Weight >= Final setting – Set point 1 setting
SP2: “0” if Weight >= Final setting – Set point 2 setting
SP3: “0” if Weight >= Final setting – FF CPS.setting
     Weight: Weight for Over/Under comparison