5.DISPLAY SETTINGS
57
5-11. Digital Tare Subtraction
This function enables you to subtract arbitrary value (as tare) from Net weight.
Set a value for tare (m+15, m+16 CH) and set the Digital tare subtraction bit to
“1” to perform Digital tare subtraction.
5-12. Restriction on Tare Subtraction
The user can apply some restrictions on the action of Digital tare subtraction and
One-Touch Tare Subtraction.
Tare value read
Specifies condition for reading in tare value.
 Always: F159 can read in tare value anytime.
 Stable: F159 read in tare value only when stable bit
(10th bit of n+5 CH) is raised “1”.
Range of Tare Subtraction
Specifies allowable tare range for subtraction.
 Whole range: any value is acceptable as tare
 0<tare<=Capacity: a value within this range is acceptable
10
3
10
2
10
1
10
0
Preset tare value: 0-99999
10
4
m+15
m+16
10
0
10
0
10
0
10
0
Digital tare subtraction
m+29
2Relay selection
1Digital tare subtraction ON
0Digital tare subtraction OFF
Avg. count of free fall compensation
Free fall compensation
Free fall compensation coefficient