- 15 -
2.4 Technical data table – Models CU600, CU700, CU800
2.4.1 Performance
R22
Model CU600 CU700 CU800
Watt 17585 21102 24619
Cooling capacity
Btu/h 60000 72000 84000
Watt 17790 21249 24912
Heating capacity
Btu/h 60700 72500 85000
Power Consumption - cooling Watt 7700 9500 10000
Power Consumption - Heating Watt 7100 8000 9500
Operating Current (cooling/Heating)
See note 3
Amp 12.9/11.9 16.0/13.4 16.8/16.0
E.E.R - Energy Efficiency Ratio Cooling 7.8 7.6 8.4
C.O.P - Coefficient Of Performance Heating 2.5 2.6 2.6
Refrigerant Charge gr. 5010 6050 7050
Moisture Removal Lit/h 7.8 8.8 10.2
Power Supply V/Ph/Hz 400V, 3Ph, 50Hz
Condensate Lines - Drain Ф-mm (in) 22 (7/8")
Time Delay Fuse Amp. 3xC-20 3xC-25 3xC-32
R407c
Model CU600 CU700 CU800
Watt 17291 20515 24180
Cooling capacity
Btu/h 59000 70000 82500
Watt 17410 20650 24200
Heating capacity
Btu/h 59400 70500 82570
Power Consumption - cooling Watt 7500 9300 9800
Power Consumption - Heating Watt 7300 8000 9400
Operating Current (cooling/Heating)
See note 3
Amp 12.6/12.2 15.6/13.4 16.4/15.8
E.E.R - Energy Efficiency Ratio Cooling 7.9 7.52 8.4
C.O.P - Coefficient Of Performance Heating 2.4 2.6 2.57
Refrigerant Charge gr. 5100 6000 7100
Moisture Removal Lit/h 7.8 8.8 10.2
Power Supply V/Ph/Hz 400V, 3Ph, 50Hz
Condensate Lines - Drain Ф-mm (in) 22 (7/8")
Time Delay Fuse Amp. 3xC-20 3xC-25 3xC-32
Notes:
1. Nominal cooling capacity based on indoor air temp.
27ºC db/19.5ºC wb and outdoor air temp. 35ºC db/24º wb.
2. Nominal heating capacity based on indoor air temp.
21ºC db and outdoor air temp. 7.5ºC db/6.1ºC wb.
3. Operating current at the most loaded phase.