2.5 Technical data table – Models CU1000, CU1200, CU1400
2.5.1 Performance
R22
Model CU1000 CU1200 CU1400
Watt 28341 35258 42204
Cooling capacity
Btu/h 96700 120300 144000
Watt 28517 35610 42614
Heating capacity
Btu/h 97300 121500 145400
Power Consumption - cooling Watt 11500 14000 17000
Power Consumption - Heating Watt 11000 13300 16100
Operating Current (cooling/Heating)
See note 3
Amp 19.3/18.5 23.5/22.3 28.6/27.1
E.E.R - Energy Efficiency Ratio Cooling 8.4 8.6 8.47
C.O.P - Coefficient Of Performance Heating 2.6 2.67 2.64
Refrigerant Charge gr. 8100 10000 12000
Moisture Removal Lit/h 11.7 14.6 16
Power Supply V/Ph/Hz 400V, 3Ph, 50Hz
Condensate Lines - Drain Ф-mm (in)
28 (1
")
Time Delay Fuse Amp. 3xC-32 3xC-40 3xC-40
R407c
Model CU1000 CU1200 CU1400
Watt 27842 34583 41324
Cooling capacity
Btu/h 95000 118000 141000
Watt 28000 34500 41500
Heating capacity
Btu/h 95540 117700 141600
Power Consumption - cooling Watt 11300 13800 16700
Power Consumption - Heating Watt 11100 13000 15800
Operating Current (cooling/Heating)
See note 3
Amp 19.1/18.6 23.2/21.8 28.0/26.5
E.E.R - Energy Efficiency Ratio Cooling 8.4 8.55 8.44
C.O.P - Coefficient Of Performance Heating 2.52 2.65 2.62
Refrigerant Charge gr. 8200 10200 120300
Moisture Removal Lit/h 11.7 14.6 16
Power Supply V/Ph/Hz 400V, 3Ph, 50Hz
Condensate Lines - Drain Ф-mm (in)
28 (1
")
Time Delay Fuse Amp. 3xC-32 3xC-40 3xC-40
Notes:
1. Nominal cooling capacity based on indoor air temp.
27ºC db/19.5ºC wb and outdoor air temp. 35ºC db/24º wb.
2. Nominal heating capacity based on indoor air temp.
21ºC db and outdoor air temp. 7.5ºC db/6.1ºC wb.
3. Operating current at the most loaded phase.