parameter descriptions vacon
•
101
9
Figure 9.2: Programmable U / f curve
1.10 F
IELD
WEAKENING
POINT
The field weakening point is the output frequency at which the output voltage
reaches the value set with par. 1.11.
1.11 F
IELD
WEAKENING
POINT
VOLTAGE
Above the frequency at the field weakening point, the output voltage remains
at the value set with this parameter. Below the frequency at the field weaken-
ing point, the output voltage depends on the setting of the U / f curve param-
eters. See parameters 1.9-1.14 and Figures 9.1 and 9.2.
When the parameters 1.1 and 1.2 (nominal voltage and nominal frequency of
t
he motor) are set, the parameters 1.10 and 1.11 are automatically given the
corresponding values. If you need different values for the field weakening
point and the voltage, change these parameters after setting the parameters
1.1 and 1.2.
1.12 U /
F
MIDDLE
POINT
FREQUENCY
If the programmable U / f curve has been selected with the parameter 1.9, this
parameter defines the middle point frequency of the curve. See Figure 9.2.
1.13 U /
F
MIDDLE
POINT
VOLTAGE
If the programmable U / f curve has been selected with the parameter 1.9, this
parameter defines the middle point voltage of the curve. See Figure 9.2.
1.14 Z
ERO
FREQUENCY
VOLTAGE
This parameter defines the zero frequency voltage of the curve. See Figures
9.1 and 9.2.