3. OPTEA/OPTE9 ETHERNET BOARD TECHNICAL DATA
3.1 General
3.2 Cables
For connecting the fieldbus Ethernet boards, use only Ethernet cables that meet at least the
requirements of category 5 (CAT5) according to EN 50173 or ISO/IEC 11801.
Table 6. Technical data
General Board name OPTEA/OPTE9
Ethernet connections
Interface Two RJ-45 connectors
Transfer cable Shielded Twisted Pair (STP) CAT5e
Communications
Speed 10 / 100 Mb
Duplex half / full
Default IP-address By default the board is in DHCP mode
Protocol Modbus TCP, Modbus UDP, Profinet I/O, EtherNet/IP
Environment
Ambient operating tem-
perature
-10°C…50°C
Storing temperature -40°C…70°C
Humidity <95%, no condensation allowed
Altitude Max. 1000 m
Vibration 0.5 G at 9...200 Hz
Safety Fulfills EN50178 standard