APPENDIX 1 - VACON® IO DATA DESCRIPTION vacon • 211
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
11
11.8 FIELDBUS PROCESS DATA MAPPING AND SCALING
This chapter describes how standard applications map process data out items by default. For
further details, see the AC drive's Application Manua, especially when not using standard
application.
Table 213. Process data output mapping defaults for VACON
®
100 family
*Scaling is based on drive nominal power. Scaling can be seen from Table 217.
Table 214. Process data output mapping defaults for VACON
®
NXP (standard applications)
Table 215. Process data output mapping defaults for VACON
®
20 X/CP (standard applications)
*Scaling is based on drive nominal power. Scaling can be seen from Table 217.
PD Out Mapped Application Data ID Unit Scale
1 Output frequency 1 Hz 0.01 Hz
2 Motor speed 2 rpm 1 rpm
3 Motor current 3 A Varies*
4 Motor torque 4 % 0.1%
5Motor power 5%0.1%
6Motor voltage 6V0.1 V
7DC link voltage 7V1 V
8 Last active fault code 37 - -
PD Out Mapped Application Data ID Unit Scale
1 Output frequency 1 Hz 0.01 Hz
2 Motor speed 2 rpm 1 rpm
3 Motor current 45 A 0.1 A
4 Motor torque 4 % 0.1%
5Motor power 5%0.1%
6Motor voltage 6V0.1 V
7DC link voltage 7V1 V
8 Last active fault code 37 - -
PD Out Mapped Application Data ID Unit Scale
1 Output frequency 1 Hz 0.01 Hz
2 Motor speed 2 rpm 1 rpm
3 Motor current 3 A Varies*
4 Motor torque 4 % 0.1%
5Motor power 5%0.1%
6Motor voltage 6V0.1 V
7DC link voltage 7V1 V
8 Last active fault code 37 - -