vacon • 212 APPENDIX 1 - VACON® IO DATA DESCRIPTION
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Table 216. Process data output mapping defaults for VACON
®
20 (standard application)
*Scaling is based on drive nominal power. Scaling can be seen from Table 217.
Table 217. Current scaling based on nominal power
Default process data out mapping can be changed in standard applications.
Table 218. FB Process data out mapping
1) Only in applications and option boards supporting fast or extended communication modes with
VACON
®
NXP. See Chapter 16 "Appendix 6 - Fieldbus option board communication".
2) Multipurpose application.
3) Currently only in VACON
®
100 family internal protocols.
PD Out Mapped Application Data ID Unit Scale
1 Frequency reference 25 Hz 0.01 Hz
2 Output reference 1 Hz 0.01 Hz
3 Motor speed 2 rpm 1rpm
4Motor voltage 6V0.1 V
5 Motor torque 4 % 0.1%
6 Motor current 3 A Varies*
7Motor power 5%0.1%
8DC link voltage 7V1 V
Nominal power Current scale
< 5 kW 0.01 A
5-100 kW kW 0.1 A
> 100 kW 1 A
Parameter name
Drives
VACON
®
100
family
VACON
®
NXP
2)
VACON
®
20
VACON
®
20 X/
CP
Path ID Path ID Path ID Path ID
FB DataOut 1 Selection P3.6.1 852 P2.9.3 852 P10.1 852 P11.1 852
FB DataOut 2 Selection P3.6.2 853 P2.9.4 853 P10.2 853 P11.2 853
... ... ... ... ... ... ... ... ...
FB DataOut 8 Selection P3.6.8 859 P2.9.10 859 P10.8 859 P11.8 859
FB DataOut 9 Selection
1), 3)
P3.6.9 890 P2.9.12 558 - - - -
FB DataOut 10 Selection
1), 3)
P3.6.10 891 P2.9.13 559 - - - -
... ... ... ... ... - - - -
FB DataOut 16 Selection
1), 3)
P3.6.16 897 P2.9.18 565 - - - -