EasyManua.ls Logo

Vacon optea - Example 3 - Exception Response

Vacon optea
253 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
vacon • 92 Modbus TCP / Modbus UDP
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
7.6.3 Example 3 - Exception response
In an exception response, the Slave sets the most-significant bit (MSB) of the function code to 1. The
Slave returns an exception code in the data field.
Command Master - Slave:
Message frame:
Exception response
Answer Slave - Master:
Reply frame:
ADDRESS 01 hex Slave address 1 hex (= 1)
FUNCTION 04 hex Function 4 hex (= 4)
Starting address HI 17 hex Starting address 1770 hex (= 6000)
DATA Starting address LO 70 hex
No. of registers HI 00 hex
Invalid number of registers 0005 hex (=
5)
No. of registers LO 05 hex
ERROR CHECK CRC HI 34 hex
CRC LO 66 hex CRC 3466 hex (= 13414)
01 04 17 70 00 05 34 55
ADDRESS 01 hex Slave address 1 hex (= 1)
FUNCTION 84 hex Most significant bit set to 1
DATA Error code 04 hex Error code 04 => Slave device failure
ERROR CHECK CRC HI 42 hex
CRC LO C3 hex CRC 42C3 hex (= 17091)
01 84 04 42 C3

Table of Contents

Related product manuals