9.2.1.5 Ethernet Link Object, Class 0xF6
Ethernet Link Object provides interface to Ethernet link counters and attributes. With this object,
user can retrieve for example link speed.
Table 124. Ethernet Link Object
Class name Ethernet Link Object
Class identifier
246
d
/ F6
h
Class
Attributes
Id Access rule Name Datatype Description
1 Get Revision UINT Class revision (4)
2 Get Max Instance UINT
Maximum instance number
(2)
3Get
Number of
Instances
UINT
Number of object instances
(2)
Class Ser-
vices
Id Name Description
1 Get_Attributes_All
Returns content of all (implemented)
attributes in the class.
14
d
0E
h
Get_Attribute_Single Used to read single attribute value.
Instance
Attributes
Id Access rule Name Datatype Description
1 Get Interface Speed UDINT
Interface speed currently in
use
2 Get Interface Flags DWORD Interface status flags
3Get
Physical
Address
ARRAY of 6
USINTs
MAC layer address
4Get
Interface Coun-
ters
STRUCT of
11 UDINTs
Interface counters. See
Table 126
5 Get Media Counters
STRUCT of
12 UDINTs
Media specific counters.
See Table 127
7 Get Interface Type USINT
Type of interface: twisted
pair, fiber, internal, etc
8 Get Interface State USINT
Current state of the inter-
face: operational, disabled,
etc
9 Get/Set Admin State USINT
Administrative state: ena-
ble, disable
10
d
0A
h
Get Interface Label
SHORT
STRING
Human readable identifica-
tion