EtherNet/IP vacon • 177
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
9
For the OPTE9, the revision of the object is 2.
9.2.2.4.1. CHANGES FROM REVISION 1 TO REVISION 2
The attributes FaultCode and FaultDay were changed from 8 bit to 16 bit.
9.2.2.4.2. CLASS ATTRIBUTES
Class Attribute “Revision”
This attribute presents the revision of the Fault History Object which is implemented by the device.
The current revision is 2.
Class Attribute “Max Instance”
This attribute presents the maximum number of instances that can exist of the Fault History Object
in the device. The maximum value is 40.
Table 152. Fault history object
Class name Fault history object
Class identifier
162
d
/ A2
h
Class
Attributes
Id Access rule Name Datatype Description
1 Get Revision UINT Class revision (2)
2GetMax InstanceUINT
Maximum instance number
(40)
3Get
Number of
Instances
UINT
Number of object instances.
Depends on drive type.
Class Ser-
vices
Id Name Description
1 Get_Attributes_All
Returns content of all (implemented)
attributes in the class.
5 Reset Reset fault history
14
d
0E
h
Get_Attribute_Single Used to read single attribute value.
Instance
Attributes
Id Access rule Name Datatype Description
1 Get FaultCode UINT Fault code
2Get FaultIDUINTFault ID
3 Get FaultYear UINT Fault date: Year
4 Get FaultMonth USINT Fault date: Month
5Get FaultDayUINTFault date: Day
6Get
FaultMillisAfter
Midnight
UDINT
Fault date: Time, millisec-
onds after midnight
Instance
Services
Id Name Description
1 Get_Attributes_All
Returns content of all (implemented)
attributes in the instance
14
d
0E
h
Get_Attribute_Single Used to read single attribute value