11
vacon • 206 APPENDIX 1 - VACON® IO DATA DESCRIPTION
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
1) This functionality can be enabled/disabled by application from drive parameters.
Table 207. FBFixedControlWord modifications in VACON
®
NXP
10 Jogging 1
0 No action.
1 Jogging request with jogging reference 1.
11 Jogging 2
0 No action.
1 Jogging request with jogging reference 2.
12 Quick stop
0 No action.
1 Drive executes quick stop / emergency stop.
13 Reserved
0-
1-
14 Reserved
0-
1-
15
Master connected
1)
0
Only in NXP. Fieldbus sets this bit to zero when it
detects that there is no connection to master.
1
Only in NXP. Fieldbus sets this bit to one when it
detects valid connection from the master.
Bit Function Description
3Fieldbus DIN1
0 Fieldbus DIN 1 off
1 Fieldbus DIN 1 on
4Fieldbus DIN2
0 Fieldbus DIN 2 off
1 Fieldbus DIN 2 on
5Fieldbus DIN3
0 Fieldbus DIN 3 off
1 Fieldbus DIN 3 on
6Fieldbus DIN4
0 Fieldbus DIN 4 off
1 Fieldbus DIN 4 on
7Fieldbus DIN5
0 Fieldbus DIN 5 off
1 Fieldbus DIN 5 on