Valor H6 - Venting Considerations When Framing

Default Icon
102 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
*Approx. 66-1/2” [1689 mm] with 24” vent pipe
48” [1219 mm] to underside of combustible cavity
24” pipe section
6WDQGR΍
Fireplace -
Left Side View
Note: Min. 24” total
rise required
48” [1219 mm] to underside of combustible cavity
Approx. 35-3/4” [908 mm]
*Approx. 69-1/2” [1765 mm] with 24” vent pipe
Fireplace -
Left side view
24” pipe section
Note: Min. 24” total
rise required
Planning Framing
Framing with Vertical Takeo
Framing with Horizontal Takeo
Venting Considerations When
Framing
*Notes—ALL venting considerations
Dimensions of venting are based on
using DuraVent elbows. Elbow curve
radius dimensions will vary when using
other brands. In general, other brands
have slightly bigger radius.
3 inches clearance to combustibles
required above horizontal pipe. Slope
horizontal pipe upwards 1/4 inch per
foot. 1 inch clearance required around
sides and bottom of horizontal pipe and
around vertical pipe.
When calculating e ective pipe lengths
subtract approximately 1-1/2 inch for
pipe joint - for example, a 12 inches pipe
section will add approximately 10-1/2
inches overall when connected.