EasyManua.ls Logo

VAMP 257 - Page 111

VAMP 257
194 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VAMP Ltd Feeder and motor manager
Technical description
VAMP 257
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
69
The minimum operation time is always limited by the setting
parameter t
Min
. In the example of Figure 2.3.22-4 the fastest
operation time, 0.15 s, is achieved when the slope is 2 Hz/s or
more. The leftmost curve in Figure 2.3.22-3 shows the inverse
characteristics with the same settings as in Figure 2.3.22-4.
Figure 2.3.22-3 Three examples of possible inverse df/dt operation time
characteristics. The slope and operation delay settings define the knee
points on the left. A common setting for t
Min
has been used in these three
examples. This minimum delay parameter defines the knee point positions
on the right.
0.75 Hz/s
2.0 Hz/s
FREQUENCY
(Hz)
49.7
START
TRIP
Settings:
df/dt = 0.5 Hz/s
t=0.60s
t=0.15 s
Min
0.00 0.450.30
50.0
TIME
(s)
ROCOF3_v3
1.0 Hz/s
0.5Hz/s
0.15 0.60
Figure 2.3.22-4 An example of inverse df/dt operation time. The time to trip
will be 0.3 s, although the setting is 0.6 s, because the average slope 1 Hz/s
is steeper than the setting value 0.5 Hz/s.

Table of Contents

Related product manuals