EasyManua.ls Logo

VAMP 257 - Page 110

VAMP 257
194 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VAMP 257 Feeder and motor manager
Technical description
VAMP Ltd
68
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Definite operation time characteristics
Figure 2.3.22-1 shows an example where the df/dt pick-up
value is 0.5 Hz/s and the delay settings are t=0.60 s and
t
Min
=0.60 s. Equal times t == t
Min
will give a definite time delay
characteristics. Although the frequency slope fluctuates the
stage will not release but continues to calculate the average
slope since the initial pick-up. At the defined operation time, t
= 0.6 s, the average slope is 0.75 Hz/s. This exceeds the setting,
and the stage will trip.
At slope settings less than 0.7 Hz/s the fastest possible
operation time is limited according the Figure 2.3.22-2
Figure 2.3.22-2 At very sensitive slope settings the fastest possible
operation time is limited according the figure.
Inverse operation time characteristics
By setting the second delay parameter t
Min
smaller than the
operational delay t, an inverse type of operation time
characteristics is achieved (Figure 2.3.22-3). Figure 2.3.22-4
shows an example, where the frequency behaviour is the same
as in the first figure, but the t
Min
setting is 0.15 s instead of
being equal with t. The operation time depends of the
measured average slope according the following equation.
Equation 2.3.22-1
s
ts
t
SETSET
TRIP
=
where
t
TRIP
= Resulting operation time (seconds).
s
SET
= df/dt i.e. slope setting (hertz/seconds).
t
SET
= Operation time setting t (seconds).
s = Measured average frequency slope (hertz/seconds).

Table of Contents

Related product manuals