Series 65  INSTALLATION 
 
963283EA  Edition 2019-05-03  45/
 
 
 
 “Sensor Crossover” defines the behavior when the actual pressure is around the upper limit of the low 
range sensor and define what sensor signal is used for building the Actual Pressure. 
Parameter  Description 
Execution method of the transient area from one sensor to the other: 
 
0:  Soft Switch    Actual Pressure is a summation of the 
pressure value of sensor 1 and sensor 2. 
1:  Hard Switch   Actual Pressure is the value of sensor 1 or 
2:  Target 
Pressure   
During pressure control: If Target Pressure 
falls into low range sensor, the low sensor is 
used for Actual Pressure. In other case the 
high range sensor is used. 
During position control: ‘Soft Switch’ is used. 
sensor] 
Threshold Low [SFS low 
sensor] 
Defines the crossover area in Crossover Mode ‘Soft Switch’ and 
‘Hard Switch’. 
 
Example:   Threshold High = 1.0 [SFS of low sensor] 
 Threshold Low = 0.9 [SFS of low sensor] 
Soft switch: 
At pressure <= 0.9*SFS low sensor: 
 Actual Pressure = Sensor low pressure 
At pressure 0.95*SFS low sensor: 
 Actual Pressure = 50% * Sensor low pressure + 50% sensor 
high pressure 
At pressure >= 1.0*SFS low sensor: 
 Actual Pressure = Sensor high pressure 
Hard switch: 
At pressure increase over 1.0*SFS low sensor: 
 Actual Pressure = Sensor high pressure after 
Delay 
At pressure decrease under 0.9*SFS low sensor: 
 Actual Pressure = Sensor low pressure after 
Delay 
Switch over delay in Crossover Mode ‘Hard Switch’, see example 
above.