1.3. Model Nomenclature
The AHU series model is fully defined by 25 digits, as represented in Table 1-1.
Table 1-1 AHU Model Nomenclature
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 2 5
F A 0 6 5 H C 1 N E 0 9 0 2 0 F 1 0 7 0 P 0 0 0 0
Digit 1,2 Product Model Digit 14 Filtration
FA Fan Array CRAC 2 G4
Digit 3, 4, 5 Air Volume 6 F6
065 65 x 1000 (CMH) Digit 15 Special Power option
Digit 6 Air Discharge 0 None
H Horizontal airflow P Power meter
V Vertical airflow S UPS
Digit 7 System type C Controller backup with Ultracap
C Chilled Water (CW) B Power meter + UPS
E CW + Free cooling E Power meter + Ultracap
X DX + Free cooling Digit 16 Enclosure options
Digit 8 Airflow F Aluminum profile and foaming board
1 EC Fan with plastic impeller M Sheet metal
2 EC Fan with metal impeller Digit 17 Mains Switch High Voltage Option
3 PFC Fan (THDi < 5%) 1 ATS C1000
Digit 9 Power Supply 3 ATS C300
N 380-415 V/3 ph/50, 60 Hz+N Digit 18 Installation Option
M 380-415 V/3 ph/50, 60 Hz without N 0 None
Digit 10 Cooling Flow S
Vibration isolators (PAD type) & Seismic restraint
bracket
E CW EVIP Digit 19 Monitoring
T CW Two way valves 7 Unity Card (Integrated)
V CW EV Digit 20 Sensors
P CW PICV 0 None
Digit 11 Humidification S Smoke Sensor
0 None E Supply air pressure dierential sensor
H Humidifier R Remote air temperature sensor
Digit 12 Display A Airflow meter
9 Global HMI 9inch X Multi sensors
Digit 13 Re-Heating Digit 21 Packaging
0 None
P
Packaging - Standard Wooden pallet and EPE
package
1 Electric heating Std 1 Stage
2 Electric heating Opt. 2 stage