Vertiv™ | Liebert® AHU | User Manual 45
4.6. Configuring Embedded Unity for BMS connectivity
From the Service menu, navigate to BMS & Teamwork Settings - IS-Unity Setup - Configuration - Network - IPv4.
Click enabled and enter the required network information.
Click Save then click Close.
A dialog appears stating the IS-Unity must be restarted. Click Restart IS-Unity. The settings take aect when Embedded
Unity restarts.
4.7. Connecting to the Unity web UI
In addition to the iCOM display, Embedded Unity supports the standard Unity web user interface (UI) for Unity configuration.
Perform the following steps to connect to the Unity web UI.
Connect a laptop to the BMS network.
Obtain the Embedded Unity IP address from the iCOM display.
Open a web browser on the connected laptop and enter the IP address.
Note: You can connect a laptop using its direct Link Local Address (LLA). Using an Ethernet cable, connect your laptop
to the P74 port on the iCOM control board. Your laptop will automatically negotiate the LLA communication settings.
In a web browser, navigate to the Unity LLA IP address: 169.254.24.7. For more information, see the Unity Card Quick
Installation Guide.
4.8. Troubleshooting
For further assistance setting up the Embedded Unity service, see the on-board help. Click the ? on the right side of the web
UI to open the Help menu and search for Unity from the iCOM Help Search bar.