EasyManua.ls Logo

Vigilant MX1-Au - Page 146

Default Icon
182 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Vigilant MX1-Au Operator Manual Document: LT0439
Page 23 October 2018 Issue 1.73
11-20
If supervision is not required, the ELD can be omitted.
The MX1 site-specific configuration must have appropriate input
supervision modes and zone mapping for these inputs to produce any
effect. There is no default action.
M
X1 CONTROLLER
2k7
A N C R E L A Y 1
VBF +
OUT 1
OUT 2
IN 1
IN 2
0 V
2k7
N/O
N/O
CLEAN
CONTACTS
Figure 11-16 Wiring General Purpose Inputs
MX1 has two protected open collector outputs which can be used for
driving low-current loads, e.g., external buzzers or relays.
Figure 11-17 shows examples of connection to a fault buzzer and an
external relay. The maximum load current is 500mA for each output, i.e.,
54 minimum load resistance. The relay back-emf suppression diode
can be any general purpose diode such as 1N4004.
Each output can be configured for open circuit fault detection if this is
required.
The MX1 site-specific configuration must have output logic or a zone
mapping for these outputs to operate. There is no default action.
VBF +
OUT 1
OUT 2
IN 1
IN 1
0V
Buzzer
Relay
MX1 MICROCONTROLLER
ANC RELAY 1
+
-
Figure 11-17 Wiring General Purpose Outputs
General
Purpose
Outputs
(OUT1,
OUT2)

Table of Contents

Other manuals for Vigilant MX1-Au