Vigilant MX1-Au Operator Manual Document: LT0439
Page 23 October 2018 Issue 1.73
To silence the Fire Brigade Panel buzzer, press the SILENCE BUZZER
key (at the MX1 panel or at the Remote FBP). The buzzer will be
Silenced. No other output or indication on the fire alarm panel will
change.
On a fire alarm the alarm devices (occupant warning system) will
generally be activated – indicated by the red ALARM DEVICES
ACTIVATED LED on. Once the alarm is investigated and the building
occupants are permitted to re-enter the building, the alarm devices can
be silenced by pressing the SILENCE/RESOUND ALARM key. However,
if it is necessary to re-sound the alarm devices then press the
SILENCE/RESOUND ALARM key again. This key will toggle the alarm
devices on and off while an alarm is present.
The Alarm Devices will automatically re-sound on a new alarm.
Note the Alarm Devices need to be silenced before the RESET or
DISABLE keys can be used.
On a networked system the MX1 may be configured to allow you to
silence/resound alarms on remote panels. Refer to Silencing Remote
Alarm Devices in Chapter 9.
Generally the alarm state latches with the MX1 so that each alarm can be
viewed later when fire-fighting personnel arrive at the fire panel.
When the alarms have been investigated and are no longer required they
can be reset.
The condition that caused each alarm must be cleared before the zone
can be reset to the normal state (for example, smoke cleared from smoke
detectors, manual call point element restored to normal, latched
detectors or MCP in the field have been disabled).
If the LCD is showing the alarm list, i.e., the first alarm on the top 2 lines
and any subsequent alarm on the next two lines, pressing RESET will
reset all zones in the alarm list. The display shows “Resetting Alarms…”,
and as each alarm is successfully reset, its entry in the list will disappear.
When the last zone is cleared, the alarm list display is cancelled.
Press F1 for the first alarm or scroll the display with NEXT until the
required zone alarm is shown on the last 2 lines of the display. Then
press F3 to select that zone.
Press RESET
Silencing/Resounding Alarm Devices
Resetting Alarms in the Alarm List
Resetting an
Individual
Alarm