Two transient-protected supervised general purpose
inputs suitable for connection to clean contact or
open collector outputs. ELD value is 1.5k-3.3k.
Each relay provides a voltage-free set of changeover
contacts, rated at 1A inductive or 2A resistive at
30VDC. Configurable contact, load or door-holder
mode supervision.
ANC1 has a demountable screw terminal header
compatible with pre-made loom LM0319 to connect
to a T-GEN 50, T-Gen 60 or T-Gen 120 tone
generator.
ANC2 has 2.5mm
2
capacity screw terminals.
A single set of voltage-free changeover contacts, 5A
resistive at 30V. Negative bias supervision of up to
three branches of wiring is possible from this relay.
ELD values are 9.1k for a single branch, 2 x 18k
for a double branch and 3 x 27k for a triple branch.
Two transient-protected general purpose open
collector 2.5mm
2
outputs which can be used to drive
loads of up to 500mA. Load mode supervision (for
O/C only) is optional on these outputs. S/C protected.
RS232. Male DB9 connector configured as DTE.
For connection to PC for diagnostics, programming,
or firmware update. Requires null-modem cable,
e.g., LM0076.
Can be connected to a modem for remote dial-in
access. This requires a straight serial cable.
RS232. Male DB9 connector configured as DTE.
Suitable for connection to a logging printer. Requires
null-modem cable for printer connection, e.g.,
LM0076.
Four 2.5mm
2
capacity screw terminals, for
connection to up to 8 remote supervised display
devices using RZDU protocol.
4 “TTL Level” serial ports on J28, J25, J26, J27
suitable for internal connection to MX Loop Cards, an
RS485 card for a Remote FBP, or a Network
Interface module such as an I-HUB, PIB or other
suitable device. Port 0 shared with RZDU Port.
Up to 999 zones can be configured.
The first 192 zones can be displayed on optional LED
displays – 32 on the keypad module and 160 on 2 x
4U modules.
Red indicator = Alarm.
Amber indicator = Fault (flashing) or Disabled
(steady)
126 Fan controls per MX1.
For AS 1668 fan controls or other functions via
programming.
Isolated and protected screw terminal, 4mm
2
capacity, for 2 wire connection to a Centaur ASE FAS
– normally-closed input. Transmits Alarm, Fault and
Disable.
10 way FRC header suitable for connection to SGD,
Super SGD.
Three sets of voltage-free changeover contacts, rated
at 1A inductive at 30V, with 2.5mm
2
capacity
terminals, for Alarm, Fault, and Disable signalling.