Page 23 October 2018 Issue 1.73
12-2
General Specifications
Inputs
GP IN1, GP IN 2
Two transient-protected supervised general purpose
inputs suitable for connection to clean contact or
open collector outputs. ELD value is 1.5k-3.3k.
Ancillary
Relay Outputs
ANC1 and ANC2
Each relay provides a voltage-free set of changeover
contacts, rated at 1A inductive or 2A resistive at
30VDC. Configurable contact, load or door-holder
mode supervision.
ANC1 has a demountable screw terminal header
compatible with pre-made loom LM0319 to connect
to a T-GEN 50, T-Gen 60 or T-Gen 120 tone
generator.
ANC2 has 2.5mm
2
capacity screw terminals.
ANC3
A single set of voltage-free changeover contacts, 5A
resistive at 30V. Negative bias supervision of up to
three branches of wiring is possible from this relay.
ELD values are 9.1k for a single branch, 2 x 18k
for a double branch and 3 x 27k for a triple branch.
Other Outputs
GP OUT 1
GP OUT 2
Two transient-protected general purpose open
collector 2.5mm
2
outputs which can be used to drive
loads of up to 500mA. Load mode supervision (for
O/C only) is optional on these outputs. S/C protected.
Serial Ports
Diag/Prog
RS232. Male DB9 connector configured as DTE.
For connection to PC for diagnostics, programming,
or firmware update. Requires null-modem cable,
e.g., LM0076.
Can be connected to a modem for remote dial-in
access. This requires a straight serial cable.
Serial Port 1
RS232. Male DB9 connector configured as DTE.
Suitable for connection to a logging printer. Requires
null-modem cable for printer connection, e.g.,
LM0076.
RZDU Port
Four 2.5mm
2
capacity screw terminals, for
connection to up to 8 remote supervised display
devices using RZDU protocol.
Serial Ports 0, 2-4
4 “TTL Level” serial ports on J28, J25, J26, J27
suitable for internal connection to MX Loop Cards, an
RS485 card for a Remote FBP, or a Network
Interface module such as an I-HUB, PIB or other
suitable device. Port 0 shared with RZDU Port.
Zones
Capacity
Up to 999 zones can be configured.
LED Indicators
The first 192 zones can be displayed on optional LED
displays 32 on the keypad module and 160 on 2 x
4U modules.
Red indicator = Alarm.
Amber indicator = Fault (flashing) or Disabled
(steady)
Fan Controls
Capacity
126 Fan controls per MX1.
Function
For AS 1668 fan controls or other functions via
programming.
Brigade
Interfaces
ASE Interface
Isolated and protected screw terminal, 4mm
2
capacity, for 2 wire connection to a Centaur ASE FAS
normally-closed input. Transmits Alarm, Fault and
Disable.
SGD Interface
10 way FRC header suitable for connection to SGD,
Super SGD.
Brigade Relays
Three sets of voltage-free changeover contacts, rated
at 1A inductive at 30V, with 2.5mm
2
capacity
terminals, for Alarm, Fault, and Disable signalling.