Vigilant MX1-Au Operator Manual Document: LT0439
Page 23 October 2018 Issue 1.73
Value x is the loop number (2 onwards).
Indicates unable to communicate with one or more AS 1668 fan
control PCBs that have been configured.
Indicates CRC fault reported from one or more AS 1668 fan
control PCBs.
Indicates unconfigured AS 1668 fan control PCBs detected.
The above points are allocated for AS 1668 fan controls when the
equipment number 248 for fan controls or other DSS functions is
configured.
This point is placed into fault if the MX1 does not receive valid
replies from the Remote FBP.
This point determines if the keypad on the Remote FBP is
enabled. If the operate state is true, the keypad will be enabled
and accept keypresses.
This point is placed into fault when the Remote FBP detects an
LED board fault.
This point is placed into fault when the Remote FBP detects a
fault on the keypad.
This point is placed into fault when the Remote FBP external fault
input has been activated.
This point is placed into fault when the Remote FBP micro test
fails.
This point is placed into fault when the Remote FBP program
CRC check fails.
This point is placed into fault when the Remote FBP RAM test
fails.
This point is placed into fault when communication channel A is
detected to be in fault. Currently not implemented.
This point is placed into fault when communication channel B is
detected to be in fault. Currently not implemented.
This point determines whether the menu for the Remote FBP will
be in Access Level 2. If the operate state is true, menu level 2
access is enabled.
This point shows the state of the alarm buzzer on the Remote
FBP, which is controlled directly by internal logic. ActInput
indicates that the alarm buzzer is active.
This point shows the state of the fault buzzer on the Remote FBP,
which is controlled directly by internal logic. ActInput indicates
that the fault buzzer is active.
This point is placed into fault when the Remote FBP LCD fails.
This point indicates as Disabled when the buzzer has been
disabled, and TestOp when the buzzer is muted.
246.2.0
through
to
246.19.0
This point is placed into ActInput if switch input n on the keypad is
active.
Equipment
245
– Fan Control
Boards
Equipment
246
– Remote
FBP