Issue 1.73 23 October 2018 Page 4-7
System Events Text
History Reset
Non-volatile event messages were all cleared (usually
following a restore failure). All previous history events
will have been lost.
History restore fail
Retrieval of non-volatile event messages failed during
system start up.
Keypad restart
The LCD/Keyboard microprocessor has restarted.
LCD logon
A user able to use Level 3 functions logged on or
logged off, respectively.
LCD logoff
Logic vars reset
The values of non-volatile logic variables were reset
(usually following a restore failure). All nonvolatile
variables will be initilised to FALSE.
Logic vars restore fail
Retrieval of non-volatile logic variables failed during
start up.
Pnt disables reset
Non-volatile point disable states were reset (usually
following a restore failure). All points will have
become ENABLED.
Pnt disables restore fail
Retrieval of non-volatile point disable states failed
during start up.
Printer events lost
The printer queue was over filled, so some events to
be printed were lost.
Reboot xxx yyyyyyyy
The MX1 has restarted software execution due to
problem xxx, yyyyyyyy shows a technical detail. If this
occurs repeatedly contact your service company.
RZDU Cmd rec'vd
An operator command was received from a connected
RZDU.
RZDU test timeout
An RZDU failed to report that a self-test passed within
4 minutes of starting.
Sw fault xxx yyyyyyyy
The MX1 internal checking routines have detected an
inconsistency that needs to be addressed. xxx,
yyyyyyyy show the details of the faults. If this occurs
contact your service company.
System running
This is a daily timestamp, indicating the system is
working.
TAP Access Granted
A temporary access password has been used to log
onto the MX1.
Time changed
The system time has been changed. The new time is
used for the event.
Warm start
The MX1 has restarted without being powered down,
for example, to change the datafile.
Zone disables reset
Non-volatile zone disable states were reset (usually
following a restore failure). All zones will have
become ENABLED.
Zn disables restore fail
Retrieval of non-volatile zone disable states failed
during start up.