EasyManua.ls Logo

Vigilant MX1-Au - Page 99

Default Icon
182 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Document: LT0439 Vigilant MX1-Au Operator Manual
Issue 1.73 23 October 2018 Page 8-13
No device in Device Fail
No unaddressed device present
Fig 8-15 Device Programming Menu No Devices in Device Fail
There must be one (and only one) device in device fail on that MX loop
for the re-addressing function to be used.
More than 1 device in Device Fail
1 unaddressed device present
Fig 8-16 Device Programming Menu Multiple Devices
The OneAtTme function can be used only when there is a single device
in Device Fail.
Device x.x in Device Fail
No unaddressed device present
Fig 8-17 No Unaddressed Device Present
Ensure that the new device has been correctly fitted to its base, or wired
into the loop, that it has not already been programmed, and that no other
device programmed to address 255 is installed on the loop.
Device x.x in Device Fail
Mismatched unaddressed device
Fig 8-18 Device Mismatch
Check that the replacement device is of the same type as the removed
one. The OneAtTme function can program only replacement devices
that are of the same type as the device they are to replace.