VIKING TECHNICAL SUPPORT 1.800.908.0884
35
# LED Status Meaning
Page 36
TS Ref#(s)
1 “ODS” OFF Normal Condition.
SOLID Obstruction event has been detected on the MASTER motor. (pg 24, 26)
11, 13, 1, 2
FLASHING Overload event has been detected on the MASTER motor. (pg 24, 26)
11, 13, 1, 2
2 “Timer”
OFF If gate is at the open limit, the Timer to close is turned OFF. (pg 24)
SOLID Timer to close is ON and counting down to close the gate. (pg 24)
FLASHING Timer is ON but is not timing out due to a conicting command. (pg 24)
9, 10
3 “Master OFF Normal Condition.
SOLID 1: The control board is sending power to the Master motor but the circuit is
open preventing the motor from running.
2: In conjunction with the ODS LED, conrms obstruction or overload event.
7, 8
11, 13, 1, 2
4 M “Limit Open”
OFF Master gate is not at the open limit position.
SOLID Master gate is at the open limit position.
5 M “Limit Close”
OFF Master gate is not at the close limit position.
SOLID Master gate is at the close limit position.
6 “Slave” OFF Normal Condition.
SOLID 1: The control board is sending power to the motor but the circuit is
open preventing the motor from running.
2:
In conjunction with the ODS LED, conrms obstruction or overload event.
7, 8
7 S “Limit Open”
OFF Slave gate is not at the open limit position.
SOLID Slave gate is at the open limit position.
8 S “Limit Close”
OFF Slave gate is not at the close limit position.
SOLID Slave gate is at the close limit position.
# LED Status Meaning
Page 36
TS Ref#(s)
9 “Power” OFF No power to control board or in Sleep Mode.
1, 23
SOLID Normal Condition.
FLASHING Operator is running on batteries only. (pg 20-21)
1, 2
10 “Low Bat” OFF Normal Condition.
SOLID Batteries are low. Check power supply to the operator. (pg 20-21)
1, 2
11 “Radio Rec” OFF Normal Condition.
SOLID Control Board is receiving an input from a device connected to the
Radio terminal. (pg 27, 37)
9, 10
12 “UL Sens” OFF Normal Condition.
SOLID
Control Board is receiving an input from a device connected to the UL
terminal. (pg 10-11, 37)
9, 10,
16,22
13 “ReOpen Sens”
OFF Normal Condition.
SOLID
Control Board is receiving an input from a device connected to the Re-Open
terminal. (pg 29, 37)
9, 10
14 “Center Loop”
OFF No voltage output on these terminals at the moment.
SOLID An input from a device connected to the Center terminal. (pg 29, 37)
9, 10
15
“Open”
OFF
Normal Condition.
SOLID An input from a device connected to the Open terminal. (pg 28, 37)
9, 10
16
“Stop”
OFF
Normal Condition.
SOLID
Control Board is receiving an input from a device connected to the Stop
terminal. (pg 28, 37)
9, 10
FLASHING
There is a problem with the required monitored sensor(s) connected to the
“UL” and/or “ReOpen input terminals. (pg 10-11)
16, 22
17 “Close” OFF Normal Condition.
SOLID An input from a device connected to the Close terminal. (pg 28, 37)
9, 10
18 “Magnetic Lock” OFF
At Closed Limit and Magnetic Lock Relay state is closed across “COM” &
“N.C.”. (pg 31). Gate should be at the Close Limit.
SOLID
Not at Closed Limit and Magnetic Lock Relay state is closed across “COM” &
“N.O.”. (pg 31). Gate should not be at the Close Limit.
19 “Aux. Pwr” OFF No voltage output on these terminals at the moment.
SOLID There is 24VDC output on these terminals at the moment.
20 “Siren” OFF Normal Condition.
SOLID Second consecutive obstruction has been detected. (pg 24, 26)
11, 13, 1, 2
FLASHING Batteries are critically low.
1, 2
E1
“AC VOLTAGE INPUT”
SOLID Normal Condition.
OFF Incoming power to the EMI Board is not sufcient..(pg 20)
1
E2
“PROTECTION WORKING”
SOLID Normal Condition.
OFF EMI Board is damaged and circuit is not protected . Replace EMI Board.
E3
“AC VOLTAGE OUTPUT”
SOLID Normal Condition.
OFF There is no output voltage from the EMI Board.
2
TROUBLESHOOTING