4. Programming
60 D-307083 PowerMaster-360R Installer's Guide
Configuration instructions
The PowerMaster-360R can be configured to provide a delay before reporting an alarm to the
monitoring station (not applicable to alarms from FIRE, 24H SILENT and EMERGENCY
zones). During this delay period, the siren sounds but the alarm is not reported. If the user
disarms the system within the delay time, the alarm is aborted. You can activate the feature
and select the Abort Time interval.
Options: in 00 (default in USA)/15/30(default)/45/60 seconds; in 2/3/4 minutes
The PowerMaster-360R can be configured to provide a Cancel Alarm time window that starts
upon reporting an alarm to the Monitoring Station. If the user disarms the system within that
cancel alarm time, a cancel alarm message is sent to the Monitoring Station indicating that the
alarm was canceled by the user.
Options: not active (default in USA); in 1/5 (default)/15/60 minute(s) and in 4 hours.