4. Programming
D-307083 PowerMaster-360R Installer's Guide 59
Configuration instructions
Define the cancel alarm period that starts upon reporting an alarm to the Monitoring Station.
If the user disarms the system within that time period, a cancel alarm message is sent to
the Monitoring Station.
Options: in 5 (default)/15/60 minutes; in 4 hours
Define whether a special beep will sound when an alarm cancel event is sent to the
monitoring station.
enable (default) and disable
Define that when the user disarms the system within the allowed abort interval a special beep
will sound to indicate no alarm transmission.
enable (default) and disable
13:OPERATION MOD
05:OTHERS SETUP
Enter the 05:OTHERS SETUP menu to configure its settings.
Configuration instructions
Certain regulations require that when the system is armed in AWAY mode, it may not be
disarmed from the outside of the house (such as by keyfobs) before entering the protected
premises and activating an Entry Delay zone. To answer this requirement, the PowerMaster-
360R provides you with the following configurable options to disarm the system:
any time (default) – the system can be disarmed at all times from all devices.
on entry wrless – During entry delay, the system can be disarmed only using keyfob or prox
operated devices.
entry + away kp. – During entry delay by code, the system can be disarmed only using
PowerMaster-360R Virtual or Touch Keypad.
on entry all. – During entry delay, the system can be disarmed using keyfobs or by code
using the PowerMaster-360R Virtual or Touch Keypad.
The Exit Delay time can be further adjusted according to your preferred exit route. The control
panel provides you with the following Exit Mode options:
A: normal (default) - The exit delay is exactly as defined.
B: restart>reentry - The exit delay restarts when the door is reopened during exit delay. The
restart occurs once only. Restarting the exit delay is helpful if the user re-enters
immediately after going out to retrieve an item that he left behind.
C: end by exit - The exit delay expires (ends) automatically when the exit door is closed
even if the defined exit delay time was not completed.
Options: normal (default); restart>reentry and end by exit.
Define a specific time period that if 2 successive alarms occur, the second alarm will be
considered as a confirmed alarm, (see RPT CNFM ALRM below).
Options: disable (default in USA); in 30/45/60 (default)/90 minutes
Define whether the system will report a confirmed alarm.
report disabled (default) - The system will not report a confirmed alarm.
report enabled - The system will report a confirmed alarm.
08:ENTRY DELAY 1
09:ENTRY DELAY 2
Two different entry delays allow the user to enter the protected site (while the system is in the
armed state) via 2 specific doors and routes without causing an alarm.
Following entry, the user must disarm the control panel before the entry delay expires. Slow-
rate warning beeps start sounding once the door is opened, until the last 10 seconds of the
delay, during which the beeping rate increases. Locations No. 1 (entry delay 1) and 2 (entry
delay 2) allow you to program the length of these delays.
Options : 00/15 (ENTRY DELAY 2 default)/30 (ENTRY DELAY 1 default)/45/60 seconds;
3/4 minutes