4. Programming
D-307083 PowerMaster-360R Installer's Guide 33
Configuration instructions
perform the Fire/Emergency function.
You can also determine that if no key is pressed during more than 30 seconds the date and time
will appear on the display. You can determine that normal display will return after pressing the
button followed by entering user code (Clock - by Code) or after pressing any key
(Clock - by Key). For further information, see the User's Guide, Chapter 1, Screen Saver Mode.
Options: OFF (default); Text - by code; Text - by Key; Clock - by Code; Clock - by Key.
Note:
1. To comply with EN requirements, refresh by code must be selected.
2. For Fire and Emergency keys, the first key press will produce the status display and will also
perform the Fire/Emergency function.
4.5.7 Configuring jamming and supervision (missing device)
The following table provides you with a detailed description of each option and its Options. To select an option and
change its setting (configuration) – refer to section 4.5.1.
Configuration instructions
Define whether jamming (continuous interfering transmissions on the radio network) will be
detected and reported or not. If any of the jam detection options is selected, the system will
not allow arming under jamming conditions. The PowerMaster-360R provides several jam
detect and reporting options to comply with the following standards:
Note: Jamming is identified by the message system jammed displayed on the Virtual or
Touch Keypad.
Detection and Reporting occurs when:
There is continuous 20 seconds of jamming
There is an accumulated 30 seconds of jamming within 60 sec.
Like EN (30/60) but the event will be reported only if the jamming
duration exceeds 5 minutes.
No jamming detection and reporting.
To comply with EN requirements, EN 30/60 must be selected.
To comply with UK Class-6 requirements, class 6 (30/60) must be selected.
62:MISSING REPRT
Previously known as
SUPERVISION
Define the time window for reception of supervision (keep alive) signals from the various
wireless peripheral devices. If any device does not report at least once within the selected
time window, a MISSING alert is initiated.
Options: after 1/2/4/8/12 (default) hour(s); and disabled.
Note: To comply with EN requirements, 1 hour or 2 hours must be selected.
Define that in case of a supervision trouble (i.e. a device is missing - see 62: MISSING
REPRT) whether the system will continue to operate as normal or the system status will
become Not Ready (upon missing) for as long as the Missing trouble exists.
Options: normal (default) and if missing dev.
64:MISS/JAM ALRM
Previously known as
BELL/REP.OPT
EN/UL standards require that if a supervision (missing) or jamming trouble occurs during
AWAY arming, the siren will sound and the event will be reported as a tamper event.
Define whether the system will behave according to EN standard or as normal (default).
Note: To comply with EN requirements EN standard must be selected.
Determine that If the smoke detector does not report at least once within a time window of
200 seconds, a MISSING alert is initiated.
Options: Disabled (default) and Enabled.