Chapter 4: Description of functions (abbreviated)
35
Function
code
Parameter name
Setting range
Default
setting
Property
P0.02
Select command
channel
0: Control via the operation panel (LED OFF)
1: Control via input terminals (LED ON)
2: Control via comunication (LED FLASHING)
0
P0.03
Frequency source
.X: Main source of frequency
1: X and Y operations (operating mode specified
by dozens)
2: Switch between X and Y
3: Switch between X and "X and Y"
4: Switching between Y and "X and Y"
X. (X a Y operation)
0: X+Y
1: X-Y
2: Maximum X a Y
3: Minimum X a Y
00
P0.04
Select the main
frequency source X
0: Digital setting (P0.10 preset frequency, can
change over UP / DOWN; clears the set
frequency when the power is turned off)
1: Digital setting (P0.10 preset frequency, can
change over UP / DOWN; saves the set
frequency when the power is turned off)
2: FIV
3: FIC
4: The rotary knob on the panel
5: Impulse setting (S3)
6: Multiple instructions
7: Simple PLC
8: PID
9: Communication interface
0
P0.05
Select the auxiliary
frequency source
Y
The same as P0.04 (X main source selection)
0
P0.06
Select the range of
auxiliary frequency
source Y
0: Considering to the max. frequency
1: Considering to the max. frequency of X
0