EasyManua.ls Logo

VYBO Electric Vector V810 - Group P1: Start; Stop Control

VYBO Electric Vector V810
106 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4: Description of functions (abbreviated)
38
Group P1: Start / Stop Control
Function
code
Parameter name
Setting range
Default
setting
Property
P1.00
Start mode
0: Direct start
1: Re-start with speed tracking
2: Pre-excitation (asynchronous motor)
0
P1.01
Speed tracking
mode
0: From stop frequency
1: From zero speed
2: From the maximum frequency
0
P1.02
Rotation tracking
speed
1-100
20
P1.03
Starting frequency
0.00Hz-10.00Hz
0.00 Hz
P1.04
Startup frequency
holding time
0.0s-100.0s
0.0s
P1.05
Startup DC braking
time/Pre- excited
time
0%-100%
0%
P1.06
Startup DC braking
current / Pre-
excited current
0.0s -100.0s
0.0s
P1.07
Acceleration/
Deceleration mode
0: Linear acceleration / deceleration
1: S-curve acceleration / deceleration A
2: S-curve acceleration / deceleration B
0
P1.08
Time portion of the
S-curve start phase
0.0% ~ (100.0%-P1.09)
30.0%
P1.09
Time portion of the
S-curve end phase
0.0% ~ (100.0%-P1.08)
30.0%

Table of Contents