Chapter 4: Description of functions (abbreviated)
74
PD.03
Response delay
0ms - 20ms
2
PD.04
Time communication limit
0.0 (invalid) 0.1s - 60.0s
0.0
PD.05
MODBUS transmission
protocol selection
_ X:MODBUS protocol
0: Non-standard MODBUS protocol
1: Standard MODBUS protocol
X _ :Reserved
1
PD.06
Current communication
resolution
0: 0.01A
1: 0.10A
0
Group PE: Reserved
Group PP: Function codes defined by user
PP.00
User password
0 - 65535
0
PP.01
Restore factory settings
00: No activity
01: Restore factory setting except motor
parameters
02: Delete records
04Restores stored user parameters
501Backs up current user parameters
0
Group C0: Torque control and parameter limitation
Function
code
Parameter name
Setting range
Default
setting
Propert
y
C0.00
Selection of control the speed
/ torque
0: Speed control
1: Torque control
0
C0.01
Torque control source settings
0: Digital setting (C0.03)
1: FIV
2: FIC
3: Reserved
4: IMPULSE setting
5: Communication setting
6: MIN (FIV,FIC )
7: MAX (FIV,FIC )
0